Integrated flame detector

Integrated flame detector

  • category:Flame detection device
  • Views:Times
  • Release date:2023-03-25 10:33:05
  • product
  • Performance
  • technical

Flame detection devices are key equipment for flame detection in power station boilers, industrial boilers, and various combustion devices during operation. This device detects the combustion condition based on the physical characteristics of the flame. When the flame combustion status does not meet normal conditions or stalls, it can provide signals (switching values, analog values) in a certain manner to serve as a fault alarm or logical judgment condition for the furnace safety monitoring system (FSSS).

JNHT series flame detection devices are divided into infrared and ultraviolet light types according to different usage situations and different spectral characteristics. According to the structural form, it can be divided into integrated type and split type. The integrated type integrates all electronic equipment of the flame detector, from the sensor to the signal interface, into the housing of the flame detector.


一体化火焰检测器

Technical parameters:

(1) Corresponding wavelength: 180 nm~390 nm (ultraviolet light), 850 nm~1700 nm (infrared light);

(2) Response time: 500 ms~6 s;

(3) Working voltage: DC24V;

(4) Working current: ≤ DC200 mA;

(5) Power consumption: ≤ 5 W;

(6) Electrical connecting wire: multi-core cable;

(7) Relay output: flame relay, passive dry contact; Alarm relay, passive dry contact;

Contact capacity: ≥ 1A, AC250 V (resistive load); ≥ 1A, DC24 V (resistive load);

(8) Analog output: DC (4-20) mA ± 0.25 mA (electrically isolated), maximum connected load: 750 Ω;

(9) Communication interface: RS485.

Under specified working conditions, it is possible to adjust the fire threshold and non fire threshold of the integrated flame detector; Under specified working conditions and when the flame input signal is valid, the integrated flame detector can display the intensity of the detected flame input signal in real time; Under specified operating conditions and when the flame input signal is valid, if the integrated flame detector is found to have a fault during self inspection, an alarm signal will be automatically given.

label

Xuzhou Jieneng Power Equipment Co., Ltd

Tel: 0516-81915686 Fax: 0516-81915687

Website: www.jinengdianli.com Email: xzjndl@163.com

Headquarters address: No. 6, Software Park Road, Quanshan District, Xuzhou City, Jiangsu Province

Manufacturing base: No. 2, Fumin Road, High tech Industrial Development Zone, Xuzhou City, Jiangsu Province


Online

24-hour service hotline:

400-1618-679

火焰检测器厂家